  • F6 - Emergency lighting

    Please provide the emergency lighting plan and the quality assurance documentation (PS1) for the entire firecell to demonstrate compliance with NZBC Clauses F6 and F8 for the new layout.

    Created 1 day, 8 hours ago

  • F7 - Fire alarm system

    Please provide comprehensive supporting documentation for the fire safety system design, including the producer statement, fire alarm layout (indicating fire alarm devices, manual call points, alarm horns, the fire information panel, etc.), fire system specifications, and a written acknowledgement confirming that a PS3 will be provided.

    Created 1 day, 8 hours ago

  • B1 - Roof truss loadbearing reactions

    The loadbearing reactions from some trusses exceed 16 kN, which is beyond the scope of NZS 3604:2011 Clause 10.2.2.2(d). Please provide further information addressing the adequacy of support and fixings for point loads (greater than 16kN) in both downward and upward directions to demonstrate the compliance with NZBC Clause B1.

    Created 1 month, 3 weeks ago

  • C - Solid fuel heater

    Please provide the specifications of the proposed free-standing fireplace and flue kit.

    Created 2 months ago

  • B1 - Bracing distribution

    Distribution of bracing elements throughout the building need to be improved as per NZS3604:2011 Section 5.4.3, bracing elements shall be located as close as possible to the corners of external walls and distributed evenly throughout the building.

    Created 5 months, 2 weeks ago

  • B1 - Bracing calculation

    When the roof pitch is greater than 25°, roof dimensions should be used to calculated the wind bracing demand. Please refer to NZS3604:2011 Section 5.2.6.

    Created 5 months, 3 weeks ago

  • B2 - Concrete strength

    Please clarify the concrete strength for the foundation system to demonstrate the compliance with NZBC Clause B2.

    Created 5 months, 3 weeks ago

  • E2 - Cavity batten compatibility

    CCA treated (H3.2) cavity battens should be avoided in direct contact with metal cladding. Please refer to E2/AS Table 21.

    Created 5 months, 4 weeks ago

  • C - SFH fireplace

    Please demonstrate how the proposed fireplace location will maintain sufficient clearance from the curtains to ensure compliance with NZS 2918:2018.

    Created 6 months ago